상세 보기
Bus Impedance Matrix Estimation Using Non-PMU Measurements
- Chang, Jae-Won;
- Lee, Gyu-Sub;
- Oh, Seaseung
Citations
WEB OF SCIENCE
5Citations
SCOPUS
5초록
A bus impedance matrix (Z(bus)) is primarily used for power system analysis. Z(bus) is typically obtained from prior information on power systems (topology and line impedance) or from the measurement data of phasor measurement units (PMUs). However, the prior power system information may be inaccurate, missing, or inaccessible, and PMUs are difficult to install for all measurements due to the high cost. Therefore, this study proposes an estimation method for Z(bus) using only non-PMU measurements. The effectiveness and practical implementation of the proposed method were verified by performing hardware-in-the-loop (HIL) experiment and simulations.
키워드
Estimation; Phasor measurement units; Voltage measurement; Sensitivity; Power system stability; Impedance; Voltage; Bus impedance matrix; Gauss iteration; non-PMU; phase angle estimation; voltage-to-power sensitivity
- 제목
- Bus Impedance Matrix Estimation Using Non-PMU Measurements
- 저자
- Chang, Jae-Won; Lee, Gyu-Sub; Oh, Seaseung
- 발행일
- 2023-03
- 유형
- Article
- 권
- 38
- 호
- 2
- 페이지
- 1743 ~ 1746