상세 보기
사무실 공간에서 광선반 적용조건에 따른 조명제어 시스템의 효율 분석
- 윤연주;
- 문진우;
- 김수영
초록
This study examines the influence of lightshelf configurations on photosensor-based lighting control in a narrow-shaped office space. Computer simulations were conducted for three options for window configurations including lightshelf under a variety of daylight conditions. Results indicate that daylight factors under lightshelves conditions were lower than that of the conditions without lightshelf, since the lightshelf functions as an overhang that blocked incoming daylight to workplanes. The amount of dimmed light for the case with and without lightshelf was approximately equal. The photosensor positioned 2 m away from window provided excessive dimming under all sky conditions and failed to provide a target illuminance. The photosensors at 5 m and 8 m away from the window were effective under clear and partly cloudy sky conditions. The control system generated excessive dimming under overcast sky and undershot the target illuminance. When lightshelves were used, the correlation between workplane illuminance and photosensor illuminance by daylight was stronger compared to the case of no lightshelf. At least, 67.8% of lighting energy savings on average was achieved by the lighting control system.
키워드
- 제목
- 사무실 공간에서 광선반 적용조건에 따른 조명제어 시스템의 효율 분석
- 제목 (타언어)
- Analysis of Lighting Control System for Applications of Lightshelf Conditions to Office Space
- 저자
- 윤연주; 문진우; 김수영
- 발행일
- 2016-04
- 저널명
- 한국생활환경학회지
- 권
- 23
- 호
- 2
- 페이지
- 310 ~ 319
- 출판사
- 한국생활환경학회
- 발행국가
- 대한민국
- 분량
- 10 페이지
- ISSN
- P 1226-1289