Supplementary control of air-fuel ratio using dynamic matrix control for thermal power plant emission

Citations

WEB OF SCIENCE

12
Citations

SCOPUS

12

초록

This paper proposes a supplementary control for tighter control of the air-fuel ratio (AFR), which directly affects the environmental emissions of thermal power plants. Dynamic matrix control (DMC) is applied to the supplementary control of the existing combustion control loops and the conventional double cross limiting algorithm for combustion safety is formulated as constraints in the proposed DMC. The proposed supplementary control is simulated for a 600-MW drum-type power plant and 1000 MW ultra-supercritical once-through boiler power plant. The results show the tight control of the AFR in both types of thermal power plants to reduce environmental emissions. © 2020 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).

키워드

Air-fuel ratioCombustion controlDynamic matrix controlPower plant controlBoiler controlCombustionFuelsThermoelectric power plants1000 MWAir fuel ratiosCombustion controlDynamic matrix controlEnvironmental emissionsPower plant controlSupercritical once-through boilersThermal power plantsPower control
제목
Supplementary control of air-fuel ratio using dynamic matrix control for thermal power plant emission
저자
Lee T.Han E.Moon U.-C.Lee K.Y.
DOI
10.3390/en13010226
발행일
2020-01
유형
Article
저널명
Energies
13
1

파일 다운로드