사무소 건물 적용 PCW 창호의 기후대별 에너지 성능 분석

Energy Performance Analysis of Photochromic Window in Office Buildings According to Climate Zone
  • 현지연; 
  • 박보랑; 
  • 최은지; 
  • 최윤경; 
  • 이춘엽; 
  • ... 문진우

초록

Purpose: This study analyzed building cooling, heating and lighting energy performance of the photochromic window (PCW) in various climate zones. Method: Office buildings were modeled using DesignBuilder software, which is a building energy analysis program, and four climate regions-Temperate climate, Tropical climate, Marine climate, and Cold climate were selected to test the performance of PCW. Result: Due to the characteristics of U-value and shading coefficient (SC) of PCW, indoor heat loss decreased in winter resulting in a decrease in heating energy consumption. On the other hand, cooling energy consumption decreased due to less transmission solar radiation in summer. As for the lighting energy consumption, the PCW's visible light transmittance (VLT) was lower than the standard clear windows (CW), thus, it was confirmed that the use of artificial lighting increased for satisfying the office indoor illumination standard. Based on the findings in this study, it can be concluded that PCW with higher VLT needs to be developed for improving energy performance as well as maintaining indoor lighting conditions.

키워드

광변색유리; 스마트창호; 건물에너지; PCW (Photochromic Window); Smart Window; Building Energy
제목
사무소 건물 적용 PCW 창호의 기후대별 에너지 성능 분석
제목 (타언어)
Energy Performance Analysis of Photochromic Window in Office Buildings According to Climate Zone
저자
현지연; 박보랑; 최은지; 최윤경; 이춘엽; 문진우
DOI
10.12813/kieae.2020.20.6.119
발행일
2020-12
저널명
KIEAE Journal
권
20
호
6
페이지
119 ~ 124