상세 보기
케이블 화재의 화염전파 해석을 위한 FDS 모델의 격자민감도 평가
- 김성찬;
- 이성혁
초록
The present study has been conducted to examine the effect of grid resolution on the predicted results for electric cable fire using pyrolysis model in FDS(Fire Dynamics Simulator, version 5). The grid independent test for different grid resolutions has been performed for a PE coating cable and the grid resolution is defined by the non- dimensional characteristic length of fire and mean grid size. The calculated maximum heat release rate and mean flame spread rate were almost constant for higher grid resolution of 20~25 and the computing time for the grid resolution takes approximately 20hours to solve flame propagation with pyrolysis model. The geometrical simplification of a electric cable dose not greatly affect on the maximum heat release rate and flame spread rate and the rectangular approximation of cable shape gives acceptable result comparing with the round cable with stepwise grid.
키워드
- 제목
- 케이블 화재의 화염전파 해석을 위한 FDS 모델의 격자민감도 평가
- 제목 (타언어)
- Assessment of Grid Sensitivity in the FDS Field Model to Simulate the Flame Propagation of an Electric Cable Fire
- 저자
- 김성찬; 이성혁
- 발행일
- 2008
- 저널명
- 한국안전학회지
- 권
- 23
- 호
- 4
- 페이지
- 30 ~ 35
- 출판사
- 한국안전학회
- 발행국가
- 대한민국
- 분량
- 6 페이지
- ISSN
- P 1738-3803