케이블 화재의 화염전파 해석을 위한 FDS 모델의 격자민감도 평가

Assessment of Grid Sensitivity in the FDS Field Model to Simulate the Flame Propagation of an Electric Cable Fire

초록

The present study has been conducted to examine the effect of grid resolution on the predicted results for electric cable fire using pyrolysis model in FDS(Fire Dynamics Simulator, version 5). The grid independent test for different grid resolutions has been performed for a PE coating cable and the grid resolution is defined by the non- dimensional characteristic length of fire and mean grid size. The calculated maximum heat release rate and mean flame spread rate were almost constant for higher grid resolution of 20~25 and the computing time for the grid resolution takes approximately 20hours to solve flame propagation with pyrolysis model. The geometrical simplification of a electric cable dose not greatly affect on the maximum heat release rate and flame spread rate and the rectangular approximation of cable shape gives acceptable result comparing with the round cable with stepwise grid.

키워드

cable fire; pyrolysis; fire simulation; fire propagation; grid sensitivity
제목
케이블 화재의 화염전파 해석을 위한 FDS 모델의 격자민감도 평가
제목 (타언어)
Assessment of Grid Sensitivity in the FDS Field Model to Simulate the Flame Propagation of an Electric Cable Fire
저자
김성찬; 이성혁
발행일
2008
저널명
한국안전학회지
권
23
호
4
페이지
30 ~ 35