Investigation of 3D manifold architecture heat sinks in air-cooled condensers

  • Kharangate C.R.; 
  • Libeer W.; 
  • Palko J.; 
  • Lee H.; 
  • Shi J.; 
  • 외 2명
Citations

WEB OF SCIENCE

18
Citations

SCOPUS

22

초록

Power plants account for a high rate of freshwater utilization in the United States. Use of air-cooled condensers (ACC) can significantly reduce or completely eliminate freshwater withdrawals for steam-electric plants but suffer from low heat transfer of single-phase air flow. In the current study, we experimentally and computationally investigate the thermal-hydraulic performance of the air-side of a traditional ACC heat sink (EVAPCO fins) and conduct an extensive comparative CFD study of a novel 3D manifolding architecture heat sink design. A parametric investigation was performed on the 3D manifold heat sinks with fin height ranging from 7.3 to 15.3 mm, three fin densities with fin pitch ranging from 1 to 3 mm, and fin angles between 0° and 45°. It is concluded that there is not a single optimal design over the range of flow rates/heat flux, and the heat sink performances are a strong function of the target operating heat flux. Overall, various manifold designs were able to offer improved COP over EVAPCO fins that covered a large range of the operating heat fluxes. Manifold designs also require less fin array material, making them a good alternative for EVAPCO ACC systems if it is desired to increase the heat flux by 3 times for the existing EVAPCO units. © 2019 Elsevier Ltd

키워드

3D manifold; Air-cooled condensers; COP; Heat sinks; Optimization; TREE-LIKE; PERFORMANCE; FLOW; EXCHANGER; ENHANCEMENT; EFFICIENCY; NETWORKS; GEOMETRY; BUNDLES; TOWER
제목
Investigation of 3D manifold architecture heat sinks in air-cooled condensers
저자
Kharangate C.R.; Libeer W.; Palko J.; Lee H.; Shi J.; Asheghi M.; Goodson K.E.
DOI
10.1016/j.applthermaleng.2019.114700
발행일
2020-02
유형
Article
저널명
Applied Thermal Engineering
권
167